ir33 platform ir33 ir33 power ir33 DIN powercompact powercompact small mastercellaUser manual

Page 2

1074866478ir33, ir33 powerir33 DINFig. 2.bENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Icon Normal operation Start up Automatic address assignment requ

Page 3

116578234112647538MasterCella powercompact, powercompact smallFig. 2.cENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Icon Normal operation Start up Autom

Page 4 - IMPORTANT WARNINGS

12ENGLISHir33 +030220441 - rel. 2.5 - 16.06.103. INSTALLATIONTo install the controller, proceed as follows, with reference to the connection diagrams

Page 5

13ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10The operating parameters can be modi ed using the front keypad, and are divided into two families: freq

Page 6 - 8. ALARMS AND SIGNALS 58

14ENGLISHir33 +030220441 - rel. 2.5 - 16.06.104.4 Displaying and setting the set point1. Press SET for more than 1 second to display the set point;2.

Page 7 - 1. INTRODUCTION

15ENGLISHir33 +030220441 - rel. 2.5 - 16.06.105.1 Parameter copying keyProgramming keys PSOPZKEY00/A0The programming keys PSOPZKEY00 (Figure 5.a) and

Page 8

16Fig. 5.fFig. 5.hFig. 5.gFig. 5.iENGLISHir33 +030220441 - rel. 2.5 - 16.06.105.2 Remote controlThe compact remote control with 22 buttons, allows dir

Page 9 - 2. USER INTERFACE

17Fig. 5.lFig. 5.mFig. 5.nFig. 5.oFig. 5.pFig. 5.qENGLISHir33 +030220441 - rel. 2.5 - 16.06.105.3 RS485 serial interfaceThe RS485 serial card option (

Page 10 - Tab. 2.b

18ir33powercompactpowercompact smallIROPZDSP00PSTCON0**B0IR00R*0000PSTCON0**00IR00R*0000IROPZSEM30MasterCellair33 DINPSTCON0**B0IR00R*0000IROPZSER30Fi

Page 11 - Tab. 2.c

19ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106. DESCRIPTION OF THE FUNCTIONS6.1 ModelsBelow is a list of the functions relating to the various models

Page 13 - Tab. 4.a

20ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.3 Switching the controller ON and OFFThe unit can be switched ON/OFF from a number of sources; keypad,

Page 14 - Tab. 4.b

21ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.4 Auxiliary output managementThe auxiliary output can be controlled by a number of sources: button, su

Page 15 - 5. ACCESSORIES

22ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10• immediate alarm from external digital input (A4, A5, A9), as this delays compressor activation;• ala

Page 16 - Tab. 5.d

23ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.6.7 DrippingThe dripping time is set by parameter dd, when the compressor is OFF and the fans are OFF.

Page 17 - 2.5 - 16.06.10

24SbrinamentoIntervallo di tempo dI (impostato) tra gli sbrinamentiNuovo intervallo di tempo (calcolato) tra gli sbrinamentiIntervallo di tempo dI (im

Page 18 - 5.9 Terminals (MasterCella)

25Sbrinamentosi salta lo sbrinamento previsto si saltano due sbrinamenti previstisi saltano tre sbrinamenti previstidI dI dI dI dI dI dI dIdIdItempodE

Page 19 - 6.1 Models

26ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.8 Pump down and low pressure6.8.1 Enabling the functionThe pump down function is activated by setting

Page 20 - Tab. 6.d

27ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.9.2 Continuous cycle in progressWhen the continuous cycle is running:• the compressor is always ON;•

Page 21 - 6.6 Defrost

28ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.10 High condensing temperature alarmIf a probe is set as a condenser probe (/A2, /A3, /A4, /A5), the c

Page 22 - 6.6.6 End multiplexed defrost

29StGrandezza controllataRREVERSErr rn rdDDIRECTzona di nonintervento==StTemperaturaRrrrdrn/2 rn/2rnRENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Fig.

Page 24

30Strd/2 rd/2Sonda virtualeReverseRRStr2Sonda virtuDirect + zona neutrard/2rd/2rn/2 rn/2DRDStrr rn/2 rn/2rnTemperaturard/2rd/2RRRReverse + zona neutra

Page 25

31ENGLISHir33 +030220441 - rel. 2.5 - 16.06.106.13 Anti-sweat heater functionThe anti-sweat heater function is used to maintain the aux1 or aux 2 outp

Page 26 - 6.8.5 Low pressure alarm (LP)

32ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Function activeFunction in antifreezeDoor switch with compressor, fan o , no light management Normal op

Page 27 - Tab. 6.g

33set point (St) Registrazione massima temperaturaAH Htd+Ad Allarme HA Durata allarme Temperatura Temposet point (St) AHBlack out Allarme HF TempoTem

Page 28 - Tab. 6.i

34ENGLISHir33 +030220441 - rel. 2.5 - 16.06.107.1 Temperature probe management parametersCode Parameter Models UOM Type Min Max Def.Pw Password MSYF -

Page 29 - 6.11 Control with dead band

35ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Example: if the room probe is in intake mode, and probe 2 in outlet mode, control can be performed based

Page 30 - Tab. 6.n

36rdSet PointOFFONDIRECT FreddoattuatoreDStrd/2 rd/2Sonda virtuale DirectENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Fig. 7.bFig. 7.a/A2: Con gurati

Page 31 - Function in antifreeze

37rdOFFONREVERSE CaldoattuatoreRStrd/2 rd/2Sonda virtualeReverseFig. 7.cENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Note:• the step associated with t

Page 32 - 6.15.2 Remote alarm signals

38accensione strumento power ONONONOFFONOFFOFFC0richiesta di interventoinsertion requestcompressorecompressorsONONOFFOFFC1richiesta inserimentoinserti

Page 33 - Temperatura

39ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10cc: Continuous cycle durationThis is the time (in hours) during which the compressor operates continuous

Page 34 - Tab. 7.b

ENGLISH IMPORTANT WARNINGSCAREL bases the development of its products on decades of experience in HVAC, on the continuous investments in technological

Page 35

40ENGLISHir33 +030220441 - rel. 2.5 - 16.06.107.4 Defrost management parametersCode Parameter Model UOM Type Min Max Def.d0 Type of defrost -SYF  ag

Page 36 - Tab. 7.c

41ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10dt2: end defrost temperature set point, auxiliary evaporatordt2 acts in the same way as parameter dt1 de

Page 37

42ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10d6: Display during defrostSpeci ed values:• d6=0 => during the defrost the instrument displays the

Page 38 - Tab. 7.d

43ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10d12: Advanced auto-adapting defrostsThis parameter is used to enable and disable the advanced defrost fu

Page 39

44set pointallarme bassa temperatura allarme alta temperaturaA0A0ALFig. 7.iENGLISHir33 +030220441 - rel. 2.5 - 16.06.10Warnings for using the continu

Page 40 - Tab. 7.e

45d5 (3)dP (2)dP (1)td5 (2)defrostdefrostdefrosttimerunit 1unit 2unit 3defrost requestdP (3)Fig. 7.lENGLISHir33 +030220441 - rel. 2.5 - 16.06.10• bot

Page 41

46Fig. 7.mENGLISHir33 +030220441 - rel. 2.5 - 16.06.10If after the door is  rst closed the light is switched o manually, the controller resumes nor

Page 42

47ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10In the  rst case, , the sensor signals the opening and the closing of the door, because, with the door

Page 43 - Tab. 7.g

48ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10A7: Delay in detecting the external alarm (multifunction input)Establishes the delay (in minutes) in det

Page 44

49Allarme “CHt” e o refrigerazione (ripristino manuale)temp. condensatorePreallarmesolo visualizzazione allarme “cht”(ripristino automatico)“AC” - “A

Page 45

5ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10 Content1. INTRODUCTION 71.1 Main features ...

Page 46

50ONOFFAmb.Amb. F1Amb. F1 - A0Evap.Evap. FantemperaturaFig. 7.oENGLISHir33 +030220441 - rel. 2.5 - 16.06.107.6 Fan management parametersCode Parameter

Page 47 - Tab. 7.h

51ON ventole prima accensione “F4” + “F5”“F4” 0.2temp. condensatoreFig. 7.pENGLISHir33 +030220441 - rel. 2.5 - 16.06.10In the event of condenser probe

Page 48 - Tab. 7.i

52Fig. 7.q84213210Tasto Set Tasto down/def Tasto up/aux Tasto prg/mute Tastiera standard 84213210Tasto SetTasto down/defTasto up/ccTasto prg/muteTasti

Page 49

53ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10H8: Select light or AUX output to activate with time band.This parameter can be used to select the outpu

Page 50 - Tab. 7.l

54ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10In: select normal, master or slave unit (masked parameter).The parameter In establishes whether the unit

Page 51

55ENGLISHir33 +030220441 - rel. 2.5 - 16.06.107.9 RTC and timed defrost management parametersNo. Code Parameter Models UOM Type Min Max Def.117 td1 De

Page 52

56ENGLISHir33 +030220441 - rel. 2.5 - 16.06.107.10 Summary table of operating parametersCode Parameter Model UOM Type Min Max Def.Pw Password MSYF - C

Page 53 - Tab. 7.r

57ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10M--- - C 0 14 3A5 Digital input 2 con guration (DI2) MSYF - C 0 14 0A6 Stop compressor from external al

Page 54 - Tab. 7.s

58ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10d__ Day **** Days * 0 11 0h__ Hours **** Hours * 0 23 0n__ Minutes **** Min. * 0 59 0tc RTC date/time se

Page 55 - Tab. 7.t

59ENGLISHir33 +030220441 - rel. 2.5 - 16.06.108.1 Summary table of alarms and signals: display, buzzer and relayThe following table describes the alar

Page 56

ENGLISH7. DESCRIPTION OF THE OPERATING PARAMETERS 347.1 Temperature probe management parameters ...

Page 57

60ENGLISHir33 +030220441 - rel. 2.5 - 16.06.108.2 Table of alarms and signals: functions enabled/disabledThe following table highlights the functions

Page 58

61ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10 NOTE:

Page 61

CAREL INDUSTRIES HQsVia dell’Industria, 11 - 35020 Brugine - Padova (Italy)Tel. (+39) 049.9716611 - Fax (+39) 049.9716600e-mail: [email protected] - w

Page 62

7Fig. 1.b - ir33DINFig. 1.c - powercompact - powercompact smallFig. 1.a - ir33, ir33 powerFig. 1.d - MasterCellaENGLISHir33 +030220441 - rel. 2.5 -

Page 63

8ENGLISHir33 +030220441 - rel. 2.5 - 16.06.10HACCPThis function, increasingly required in the refrigeration market, is included as standard on all mod

Page 64 - Agenzia / Agency:

9MasterCella ir33, ir33 DIN, ir33 power, powercompact, powercompact smallFig. 2.aENGLISHir33 +030220441 - rel. 2.5 - 16.06.102.1 DisplayICON FUNCTION